动力电源(国外英文资料)
动力电源(国外英文资料)
The total voltage 48V system is 53.5 ~ 54.7 V, and the monomer charge is 2.23 ~ 2.28 V. The total voltage 48V system is 55.2 ~ 56.4 V, the monomer charge is 2.30 ~ 2.35 V.
The limit of pressure reduction and temperature limit in the dc power supply circuit is below 1000A, which is less than 5mV per 100 ampere. Every one hundred amperes is less than or equal to 3mV. Node temperature rise shall not exceed 40 ℃.
3, the communication power supply has the communication uninterrupted and the dc uninterrupted supply two big system, the current continuous power supply is the main.
The credit switching power supply is the power transfer equipment between the municipal power grid and the communication equipment.
5, PS series intelligent high frequency switching power supply system includes large capacity ac power distribution, dc power distribution cabinet, rectifier module, monitoring module and integration (or frame) five most.
The monitoring system adopts the structure of cascade, which includes the monitoring module, the monitoring unit, the monitoring station and the monitoring center.
The contents of the room environment monitoring include: smoke, temperature, humidity, infrared, water immersion.
There are three kinds of alarm in the monitoring system: emergency warning, important alarm and general alarm.
Monitoring internal station data is transmitted by 2M signal. There are three ways of local transmission: cascade, insertion and independent transmission.
10, inverter into high frequency ac, DC output rectifier filter to the DC and ac into want to finish from a DC voltage to another kind of DC voltage conversion, so the two parts can be called the DC - DC transform.
2, correct and wrong (2 points, 20 points)
Battery cell voltage below 2.8 volts means the battery is discarded (x).
Correction: battery cell voltage under 1.8 volts means the battery is useless.
2, the unit voltage is lower than 2.18 V, and it must be recharged (x).
Correction: the unit voltag