空调维修案例(国外英语资料)
空调维修案例(国外英文资料)
Maintenance case of air conditioning refrigeration system
The refrigeration system is a fault fault often wind we repair them, fault phenomenon is all kinds of, all sorts of strange things, but still have to follow the law, have experience. Here is the air conditioning refrigeration system failure inspection procedures, although not necessary, but maintenance should follow this train of thought overhaul.
Refrigeration system overhaul points
1, observe the work inside and outside the machine: if the light display board, inside the machine is working, the output speed is normal, the fans, the compressor is running, in order to determine the problem or lead to electrical system problems without refrigeration.
2. Check the air conditioner data:
A, air conditioning, water flow, general internal drip water, continuous air conditioning is normal, but affected by environmental humidity and temperature, can only be used as a reference value.
B, inlet and outlet temperature difference, the normal temperature difference between inlet and outlet should be 12-14 degrees, but it will also be affected by environment temperature and wind speed.
The C measurement system, pipeline pressure, general refrigeration heating in low pressure 0.45Mpa-0.50Mpa, high pressure between 1.8Mpa-2.2Mpa, but the pressure to be affected by the ambient temperature, inlet air temperature is high, the exhaust pressure is high, the condensing temperature is higher, and vice versa; the greater the air conditioning load, the higher the suction pressure. The evaporation temperature (normal evaporation evaporator temperature between 5-7 degrees).
Two. Refrigeration system fault type
1, refrigeration system block: often occurs in the capillary and dry filter place, because these two places are the most narrow place in the system, common jams for three reasons: dirty block, ice jam and welding plug.
A, a dirty block generally occurs in the capillary inlet, is because of the dirt in the system (s
文档评论(0)