8.14美加大停电分析资料

ITC Analysis of Grid Collapse 8/17/2003 Precondition 8/14/03 3:06 PM High temperatures in the Midwest FirstEnergy’s (FE) 750 MW Davis-Bessie nuclear plant is down for maintenance The 550 MW FE Eastlake generating unit in Northern Ohio went offline at approximately 2:00 PM The Chamberlain- Harding transmission line feeding the city of Cleveland has just gone out of service Flows over Michigan’s interstate connections are normal 25 Minutes Later… 8/14/03 3:32 PM A second line feeding the city of Cleveland goes out of service Hanna-Juniper Transmission system near Cleveland experiences low voltage Flows on Michigan’s interstate connections remain steady 10 – 15 Minutes Later… 8/14/03 3:41 – 3:46 PM Two more transmission lines feeding Northern Ohio go out of service Star-South Canton Tidd-Canton Central Transmission system near Cleveland experiences severe low voltage Flows on Michigan’s interstate connections remain steady 20 Minutes Later… 8/14/03 4:06 PM The Sammis-Star transmission line feeding Northern Ohio from within Ohio goes out of service Flows on the ITC – FE interstate connection reverse and FE starts pulling 200 MW through Michigan 3 Minutes Later… 8/14/03 4:09 PM Two more transmission lines feeding Northern Ohio go out of service E.Lima-Fostoria Muskingum-OH Central Northern Ohio becomes electrically isolated from the rest of Ohio First Energy is suddenly pulling 2200 MW through Michigan’s Grid In less than 10 seconds the flows on the ITC – FE interstate connection jump by 2000 MW Flows on the ITC – IMO international connection reverse Voltage on the Michigan Grid begins to decline under the strain About 30 - 45 Seconds Later… 4:09:31 - 4:09:46 PM As a result of the declining voltage two power plants in Mid-Michigan with an aggregate capacity of approx. 1800 MW go offline within 15 seconds of one another Kinder-Morgan MCV Voltage begins to collapse (decline) in Michigan About 1 Minute Later… 4:10:40 - 4:10:46 PM The ITC sys

文档评论(0)

yan698698 + 关注
实名认证
内容提供者

该用户很懒,什么也没介绍

1亿VIP精品文档

相关文档