ref542plus保护器速断时间的整定跟逻辑完善

REF542plus保护器速断时间的整定和逻辑完善 REF542plus protecting devices speed time exactly makes and logic is complete 摘要: ABB公司生产的REF542plus综合保护器已在乌石化炼油厂电力系统得到广泛应用。然而, 在将该保护器运用于电动机保护时,我们发现该保护器会由于速断时间整定在该保护器的最低时限而发生误动作,同时,由于其逻辑程序存在的缺陷,往往导致速断保护占用跳闸通道的现象,造成受控的电气设备无法停机,本文就此问题提出解决办法和改进意见。 Abstract:REF542plus protecting device synthetically that ABB Company produced has been already used widely in the power system of oil plant of the dark petrochemical industry. But, should person who protect apply to motor protect, we find should person who protect can fix on because of speed broken time should minimum time limit