40 10 3199-3206 Vol.40, No.10: 3199-3206 2014 10 31 High Voltage Engineering October 31, 2014 DOI: 10.13336/j.1003-6520.hve.2014.10.036 300072 ( AMDT) AMDT ANSYS AMDT AMDT 1.6 Compact Main Insulation Structure Design of Amorphous Alloys Oil-immerse Transformer LIU Daosheng, DU Boxue, XIAO Meng (School of Electrical Engineering and Automation, Department of Electrical Engineering, Tianjin University, Tianjin 300072,China) Abstract In order to optimize amorphous alloys oil-immerse distribution transformer (hereafter referred to as AMDT) in aspects of size and economy, we designed a compact insulation structure for AMDT. The electric field distribution in AMDTs with compact or conventional main insulation structure is calculated respectively using ANSYS. Reliability of the compact main insulation structure is tested by power-frequency AC withstand voltage tests and lightning impulse tests. The simulation and test results show that the electric field of the compact main insulation structure is better distributed than that of the conventional structure, and its maximum electric field intensity is less than that of oil gap. Moreover, the breakup voltage margin of the compact main insulation structure is more than 1.6 times of the rated withstand vol