换流站阀冷系统典型问题分析.pdfVIP

  • 213
  • 1
  • 约1.67万字
  • 约 6页
  • 2019-07-10 发布于广东
  • 举报
换流站阀冷系统典型问题分析 陆 锐,何园峰,徐攀腾,姚言超,徐晟 (中国南方电网超高压输电公司广州局,广州510663 ) 摘要:结合南方电网内各直流输电工程换流站阀冷却系统运行情况,通过介绍换流阀冷却系统的基本原理 及其对直流输电系统的影响,结合实际分析了换流站阀冷系统运行中暴露出来的一些典型问题并提出了相 应处理措施。这些运行经验为未来直流输电工程阀冷却系统的设计和施工、换流站内阀冷系统的运行和维 护都提供了有益的参考。 关键词:换流站;换流阀;阀冷系统;故障;高压直流输电 Converter Station Valve Cooling System Typical Problems Analysis LU Rui ,HE Yuan-feng,XU Pan-teng ,YAO YAN-chao,XU Sheng (Guangzhou Bureau, EHV Power Transmission Company of CSG, Guangzhou 510663 ) Abstract: Combined with the operation situation of the HVDC converter valve cooling system in China Southern Power Grid,this paper introduces the principle basic principle of valve cooling system and its i nfluence on the DC transmission system in Southern Power Grid .It proposes some measures by analyzin g some valve cooling system typical problems exposed in the actual operation .The operation experience provides a useful reference for the design and construction of the cooling system of the future HVDC pr oject and the operation and maintenance of valve cooling system in the converter station. Key words:Converter station; thyristor valve ; valve cooling system; problem;HVDC 可靠运行。从换流阀流出的热水由主循环泵 0 引言 加压后送入外冷水冷却塔进行冷却,冷却后 随着西电东送工程的不断推进及直流 的水依次经过脱气罐、电加热器、高位水箱 换流站陆续投产,南方电网至今已经建成八 后再次进入换流阀进行循环冷却。此外,并 交八直的西电东送大通道,为东部地区发展 联于主循环回路的去离子回路通过离子交 提供可靠的清洁能源。直流换流站的换流阀 换器将内冷水电导率控制在定值以下。外冷 在运行中会产生大量热量,阀冷系统是换流 水系统为开放式循环系统,喷淋水泵从室外 阀的重要组成部分,它将晶闸管阀上元件产 外冷水池抽水均匀喷洒到冷却塔内换热盘 生的热量排放到阀厅外,保证晶闸管运行温 管表面来吸收内冷水热量,冷却塔持续将吸 度在正常范围[1] 。阀冷却系统故障往往会造 热后形成的水蒸汽排至大气,冷凝水回流至 成相关主设备运行工况恶化,进而导致跳闸 外冷水池以实现对内冷水连续降温的目的。 事件。本文分析了南方电网换流站运行中典 各直流输电系统中,阀水冷监控系统主