23 2 Vol.23 No.2 2009 4 Refrigeration and Air Conditioning Apr. 2009.8385 1671-6612 2009 02-083-03 ——— —— TU831 A Changes the amount of wind air-conditioning system control method contrast research He Jianping (southwest Scientific and technical university civil engineering and building institute, Chengdu, 621010) Abstract This article introduced changes the amount of wind air-conditioning systems four kind of control method control principle, the characteristic and the good and bad points. Decides the static pressure control to be simple, but the energy conservation effect is bad; Changes the static pressure control method with decides the static pressure control method to compare, the energy conservation effect is obvious, but increased the valve opening control, makes the control to be more complex, the wind valve opening signals feedback has a lag process to the air blower rotational speeds adjustment. The direct digital control method all opens when through end equipments wind valve the opening - differential pressure - discharge characteristic, air hoses current capacity aerodynamically resistance characteristic, air blowers rotational speed - lifting - discharge characteristic, satisfies the smallest static pressure control the air feeder rotational speed. The air blower total amount of wind control methods basic principle is according to the air blower law of similarity, when the air-conditioning system friction coefficient does not change, the total amount of wind and the air blower rotational speed are direct proportion