Room Temperature RCC60.1 Controller for two-pipe fan coil units Modulating PI control Output for three-position valve actuator Outputs for three-speed fan Automatic heating / cooling changeover Operating modes: normal and energy saving or OFF Operating mode changeover input for remote control Function for avoiding damage resulting from moisture Operating voltage AC 230 V Use Typical use: • Control of the room temperature in individual rooms that a eated or cooled with two-pipe fan coil units. • For opening and closing a three-position valve actuator operating on AC 230 V and for switching a three-speed fan. Suited for use in systems with • automatic heating / cooling changeover • continuous heating or cooling operation. CE1N3026en Siemens Building Technologies 12.06.2003 HVAC Products Functions The controller acquires the room temperature with its integrated sensor and maintains the setpoint by delivering three-position control ds to the valve. The controller provides PI control. The proportional band