Attachment 1: Example of a gap assessment (non-exhaustive) 附件1:差距评估实例(非详尽无遗)
Key Areas
Key Elements
Detailed CCS Elements
Annex 1 rev12 draft reference
Identified potential gaps (or documentation improvement need)
versus Annex 1 draft expectations
Key supporting Site Strategies, Rationales, Risk assessments
Include Reference, title and if possible hyperlink to the
Key Site Procedures
Include Reference, title and hyperlink to the document
Facilities, equipment, Utilities and Infrastructure Design, Qualification, Maintenance and Control
Facilities
Facilities Design
Facility design requirements (plant layout, air filtration, material of construction, cleanability, airlock design, logical and chronological activities flows )
4.1, 4.2, 4.3, 4.5, 4.6, 4.7,
4.8, 4.9
4.10, 4.11, 4.12, 4.13, 4.17
6.6
6.21
4.1 explain how controls and monitoring are scientifically justified and capable of evaluating the state of environmental conditions for cleanrooms, airlocks and pass-throughs used for material and equipment transfer
4.3 Barriers should be considered in the CCS. Any alternative approaches to the use of RABS and Isolators should be justified
Develop the current material transfer and airlocks sections using wording of 4.10, 4.11, 4.12, 4.13
To be filled out accordingly
To be filled out accordingly
HVAC system design requirements (Air Filtration/HEPA Filters, Pressure cascades, Temperature, RH, locations of air inlets outlets, ducts cleanability, air exchanges rates, alarms settings and controls ..)
4.13, 4.14, 4.15, 4.16
4.35
Develop an adequate section to cover 4.16 Setpoints and the criticality of pressure differentials should be documented within the CCS / where alarm delays are set, these should be assessed and justified within the CCS
To be filled out accordingly
To be filled out accordingly
Area Classification / Grade cascading
4.1, 4.4, 4.12, 4.13, 4.20
8.14
No gap identified
Physical segregation of activities (dedicated facility/area, use of closed systems, o
您可能关注的文档
- √ 01 Anwarul 基于ISPE GAMP5的计算机化系统验证生命周期实施.pdf
- CCS指南-附件2:CCS内容表的例子.docx
- CCS指南-附件3:污染控制策略文件的模板(示例).pdf
- CTD申报资料:创新药IND模块一--行政文件和药品信息.docx
- CTD申报资料撰写模板:模块三之3.2.P.4辅料的控制.docx
- CTD申报资料撰写模板:模块三之3.2.S.4原料药的质量控制.docx
- EMA:人用药品亚硝胺评估最终报告-2020年07月.pdf
- EMA-制药用水指南(中英文版).pdf
- EP各论中溶出度和崩解度测试的新政策 20201210.pdf
- FDA-21 CFR Part 820新版医疗器械质量管理体系法规(QMSR)征求意见稿(中文)-202202.pdf
文档评论(0)