Abstract
Abstract
dry type shell-tube evaporator is widely used in the refrigerating industry owing
to its small demand of refrigerant and steady operation.The bottleneck restricting its
wider application is in ordinary heat transfer performance.There is a view proposed
in some study that nonuniform refrigerant distribution between the pipes is a major
cause leading to invalid improvement in heat transfer performance.
In this paper,characteristic of refrigerant flow distribution for the evaporator is
studied through theoretical analysis,experimental research and numerical simulation
method respectively.And the optimized methods are put forward.
Firstly,the criteria to measure uniformity of flow distribution in dry type
shell—tube evaporator is provided in this paper.The heat transfer formula of single
tube is obtained by theoretical analysis.The effect of flow change on the evaporator is
studied.The results show that the existence of nonuniform distribution of refrigerant
in the evaporator has an impact on the heat-exchange performance.Nonuniform flow
distribution results in heat transfer enhancement.And the influence is especially
greater when wetted perimeter less than 1 under the conditions of flow distribution of
evaporator.
Then,the experimental facility for fluid distribution is established and the
experiments are carried out.Due to the limitation of experimental conditions,
simplification、析th 25 distribution tubes and air-water as medium replacement are
taken in the experiment.The following two goals are reached:the distribution of fluid
visualization results gotten and the numerical simulation of two phase flow under
same conditions validated.
A 3D model、坜th the size as the real on is explored to conduct data calculation
on the dry type shell—tube evaporator The reason of nonuniform distribution in
evaporator is analysised,the stress distribution feature in the entrance of each tube
and the turbulence area inside the tube are main factor affecting stream dis