ENGINEERING SPECIFICATION
Analog Gas Transmitters with Building Automation Systems
(CO, NO2, COMBUSTIBLES, AMMONIA)
SECTION XXXXXX GAS MONITORING AND CONTROL SYSTEM
PART 1 – GENERAL
RELATED DOCUMENTS
Applicable portions of all documents listed in the index as well as Section XXXXX apply to work of this section.
SCOPE
Work under this section of the specifications shall include the furnishing and installation of a complete gas monitoring and control system including all related accessories.
SUBMITTALS
Furnish submittal data for the following materials and equipment in accordance with the requirements of Section XXXXX “General Requirements for Mechanical Trades.”
Gas monitoring and control system.
All related devices.
ACCEPTABLE MANUFACTURERS
INTEC Controls, Inc.
PART 2 – PRODUCT SPECIFICATIONS
2.1 BUILDING AUTOMATION SYSTEM
The building automation system shall provide continuous monitoring of the designated gas levels in the assigned area and control the ventilation system in accordance with all applicable codes and standards.
The building automation system shall have the capability to accept any combination of 4-20 mA transmitters as provided by INTEC Controls, Inc.
CARBON MONOXIDE (CO) SENSOR/TRANSMITTER
The carbon monoxide sensor/transmitter shall provide monitoring of the carbon monoxide levels in the parking garage and control the ventilation system via the DDC/BA system in accordance with all applicable codes and standards.
The sensors shall be electrochemical type. The sensor/transmitter shall have plug-in technology for ease of troubleshooting and replacement of both the element and the printed circuit board. Solid-state sensors or air sampling devices shall not be acceptable.
The sensor range shall be 0-250 ppm carbon monoxide. A microprocessor-based transmitter shall generate a polarity protected, proportional 4-20 mA output signal. The wiring between the transmitter and the DDC/BA system shall be a 2-
您可能关注的文档
- e n t e r t a i n m e n t e d u c a t i o n- colby college(e n t e r t i n m e n t e d u c t i o n -科尔比学院).doc
- e q u i p m e n t a n d f i x e d m a c h i n e r y- aberdeenshire(e问u i p m e n t n d f i x e d m c h i n e r y -阿伯丁郡).doc
- e v a l u a t i o n o f b o v i n e t e a t c o n d i t i o n i n c o m m e r c i a l d a i r y h e r d s1(e v t l u i o n o f b o v i n e t e t c o n d我t i o n n c o m m e r c我一个l d r y h e r d s1).doc
- e x p e r i e n c e o n e n e r g y a n d t o u r i s m a n d e m v i r o n m e n t i n t a n z a n i a(e x p e r e n c e o n e n e r g y n d t o u r s m n d e m v i r o n m e n t我n t n z n).doc
- e x p e r i m e n t2- r a t e c o n s t a n t o f a p s e u d o- f i r s t o r d e r r e a c t i o n(e x p e r m e n t2 - r t e c o n s t n t o f p s e u d o - f i r s t o d e r r e c t i o n).doc
- e x p e r i m e n t4( organic chemistry i)- southwest college(e x p e r m e n t4(有机化学我)——西南大学).doc
- eco-industrial estates handbook(生态庄园手册).doc
- ecotecsupercharged2.0- g m media online english(ecotecsupercharged2.0 - g m媒体在线英语).doc
- electric arc furnace steelmaking- k u leuven(电弧炉炼钢- k u鲁汶).doc
- electricity guide, vol- maine(电力指南,卷——缅因州).doc
文档评论(0)