IEC 62439 High Availability Automation NetworksIEC 62439的高可用性自动化网络

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Methods for dynamic redundancy in networks IP protocol Layer 3 (network) 10s or more – unsuited for Industrial Ethernet RSTP (IEEE 802.1D) Layer 2 (bridges): 1 s typical, less in fixed topography HyperRing Layer 2 (ring) 50 ms (typical, depends on ring size) CRP Layer 2 400 ms (typical, depends on LAN size) BRP Layer 2 10 ms (typical, depends on beacon frequency) DRP Layer 2 ? RRP Layer 2 ? The switchover time of dynamic redundancy is limited by the detection time of the failure. (or rather, by the interval at which the n