Section 19. Streetlamp engineering
One, process flow
Measuring lofting to foundation pit excavation, pouring the street lamp base - laying cable - insulation test to street lamp installation, electrical equipment installation to test, debug, self-checking and completion inspection and acceptance
Second, construction method
1, foundation construction,
Using artificial cooperate with excavator in foundation pit excavation, when dig to 10 cm away from the design elevation, using artificial nap, lest overbreak, foundation pit size must comply with the design requirements. After testing qualified for anchor bolt installation of foundation pit, the anchor bolt installation location must be accurate, and strictly control the elevation, the top level for the kerbstone crest elevation + 20 cm control, pouring concrete to embedding double PVC trunking, at the same time. Concrete pouring must be done on the whole basis once, and it is strictly forbidden to water the base graded intermittently. USES the commercial concrete, concrete construction process, the laboratory must be strictly controlled for raw materials, firmly wiped out unqualified concrete, concrete casting vibrating to fully, cant leak.
Cable: meet the following requirements
(1) the cable model is yjv-1kv-5 * 25/yjv-1kv-3 * 25, which is buried in the buried floor of the p63, which is not less than 70cm.
(2) the fixed, spacing and bending radius of the cable shall conform to the regulations;
(3) the cable joints are good and the insulation should meet the requirements.
(4) when the cable is laid, the length of the cable shall be no less than 10cm of fine earth or sand, and the length of the cable shall be covered by the cable protection plate.
(5) the cable shall be protected by the DN100 galvanized steel pipe, and the cable connection well shall be set at both ends of the pipe and the cable joints.
Lamp installation regulation
(1) the lamp installation height (from the light source to the floor), the