变压器低压侧中性点接地导体截面的选择
钱中阳 (中国市政工程西北设计研究院有限公司北京分院,北京市 100037)
冯志文 (陕西省建筑设计研究院有限责任公司, 西安市 710003)
Selection of the Grounding conductor Cross Section of Neutral Point of
Transform Low-voltage Side
Qian Zhongyang (Beijing Branch,Cscec Aecom Consultants Co.,Ltd,
Beijing 100037,China)
Feng Zhiwen (Shaanxi Architectural Design Research
Institute Co.,Ltd, Xi’an 710003, China)
Abstract Based on analysis and research of the present documentation
and combined with calculation example, grounding conductor cross section
of neutral point at low-voltage side of transformer 10/0.4 kV validated.
And somen issues to which attention shall be paid during selecting cross section
are discussed.
Key words Neutral point grounding, Single-phase short circuit,
Sselectiong of cross section, Validation
摘要 通过对现有文献资料的分析研究,配以计算实例,对 10 / 0. 4 kV 变
压器低压侧中性点接地导体截面进行校验,并对截面选择应注意的一些问题进
行了探讨。
关键词 中性点接地 单相短路 截面选择 校验
对于 10 / 0.4 kV 配电变压器低压侧中性点接地,无论国家规范还是 IEC
标准,都有较严格的要求。在工程实践中,对于变压器中性点接地导体截面的选
取,可参考国标图集中专门的数据表。但笔者尚未见到有关这类表格中数据的详
细介绍和验算的文献。本文通过对现行不同国标图集的对比、分析和探讨,提出
在工程应用中需注意的若干问题。
1 设计参考依据
1.1 关于变压器低压侧中性点接地导体截面的选择,笔者能查到的文献资料
a . 《干式变压器安装》 ( 99D201-2 ) 图集第 33 页表格:变压器低压侧出
线选择。
b . 《10 kV 及以下变压器布置及变配电所常用设备构件安装》( 03D201-4 )
图集第 229 页表格:变压器低压侧出线选择。,其中提到表中数据均参考 《工业
与民用配电设计手册》和 《干式变压器安装》( 99D201-2 )图集。
c . 《建筑电气常用数据》( 04DX101-1 )图集第 4-3 页表格:变压器低压侧
出线选择。,其中 800 kV · A 变压器中性点接地导体采用 VV 电缆时规格为 1x150
2 2
mm ,而 99D201-2 和 03D201-4 中采用VV 电缆时规格为 1x120 mm 。
1
d . 《民用建筑电气设计与施工— 变配电所》( 08D800-3 )图集第 99 页表
格:变压器低压侧出线选择。,其中 800 kV · A 变压器中性点接地导体采用 BV
2 2
线时规格为 1x150 mm ,而
您可能关注的文档
最近下载
- 2025年山东劳动职业技术学院单招(语文)测试试卷通关秘籍题库.docx VIP
- 《医疗器械不良事件监测与再评价管理办法》试题及答案.docx VIP
- 基于SVI模型的期权隐含波动率曲面套利策略.pdf VIP
- 教学课件 电子信息类专业英语(第三版)李白萍.ppt
- (重庆一诊)重庆市2026届高三第一次联合诊断检测(康德卷) 物理试卷(含答案).docx
- 2024年连云港市直遴选笔试真题汇编及答案解析(夺冠).docx VIP
- 临床诊断学胸痛幻灯片.ppt VIP
- 换热器选型说明书.pdf VIP
- 江苏省南京市南京一中2025-2026高三上学期10月英语月考试题(含答案,无听力原文及音频).docx VIP
- 王承党《临床诊断学》胸痛.ppt VIP
原创力文档

文档评论(0)