太阳能板的安装Install and Mounting SolarPV (NXPowerLite)
Residential/Commercial
Residential/Commercial
RReessiiddeennttiiaall//CCoommmmeerrcciiaall
Solar PV installations
Solar PV installations
SSoollaarr PPVV iinnssttaallllaattiioonnss
Basic information and installation guides for roof
mounted systems (Ed Larsen, Building Official)
May-June 2008
City of Flagstaff/Project Review Section
Design and Permits
� A building permit is required for a Solar PV or thermal solar system.
Staff has prepared a Memorandum (Memo #106; which is periodically
updated) on the submittal requirements. These permits are not issued
over-the-counter.
� If the system is to be connected to the grid (APS utility system), then a
copy of the approved interconnect agreement and a licensed contractor
is required for the final installation and “green tag”. For off-grid or
battery systems, a licensed contractor is not necessarily required.
� If the system is not roof mounted, then the arrays must be protected
from the general public. This can be done by establishing racks at
eight (8) feet or greater above the ground level or by providing fencing
or a skirting system around the underside of the panels to prevent
contact with wiring.
� Permits are not issued over the counter, but require plan review.
Simplified drawings are allowed. A one line or block schematic is
required and a three-line wiring diagram (indicating wiring sizes and all
leads) is also required.
Design and Permits - continued
� There are some minor conflicts between Article 690 of the 2005 NEC and the
wiring sizes for various breakers. The inverter specifications should be carefully
compared to the general requirements [i.e., a PV system may only require #10s
or #12 AWG wiring on the AC side and the max current (amps) may be 30 or
less; however, the designer goes for the maximum size for the
原创力文档