钢铁厂对电力系统谐波与电压闪烁.doc

鋼鐵廠對電力系統諧波與電壓閃爍之影響分析指導教授:張文恭 博士 研 究 生:摘 要 檢討各用戶責任分界點之總和與各次諧波電流及電壓閃爍值是否超出既有之管制標準,本論文選定ADX3000及RPM分別量測台電某一次變電所161kV、4號主變壓器及161kV級鋼鐵MOF端之電壓閃爍、諧波及,管制諧波電壓閃爍管制。 量測本論文量測量測是否管制。EMTP程式之ATP版本分析本論文的貢獻包括 1)諧波及電壓閃爍管制值計算2)量測161/69kV匯流排及相關用戶MOF諧波電流及電壓閃爍值是否管制,)建立一模擬系統,分析Power System Harmonics and Flicker Analysis for Steel Plants Advisor:G.W.Chang, Ph.DStudent:.E.Hsiao Abstract To examine the total harmonic distortion of current (THDI), individual harmonic current and voltage flicker at various users’ duty point, the thesis adopts ADX3000 and RPM to measure the harmonic current, voltage flicker and power data at 161kV feeder’s terminal, the second side of the 4th main transformer of some primary substation of Taiwan Power Company and MOF point of 161kV level steel factories, and calculated the governing limits of the harmonic current and voltage flicker at each measured point according to the present standards. The thesis presents how to use the measuring instrument and its software to analyze measured data by statistical method and examines whether conformable to the present standards. Finally, the thesis will present simulations of the power transmission system by ATP edition of Electromagnetic Transients Program (EMTP) to analyze the operating condition when electric arc furnace (EAF) and filter, and discuss the transitional condition and its difference between switch-on and switch-off of the switches used by EAF and filter. The contributions of the thesis include 1) proposing a method to compute governing limits of THDI, individual harmonic current and voltage flicker, and being a reference to research in the future; 2) using the measured results from the harmonic current and voltage flicker of the 161/69kV bus and the MOF point of related users to judge whether corresponding with governing standards, and taking as background information for study in the future; 3) establishing a simulation system to analyze the stable and transition conditions of the EAF and filter.

文档评论(0)

snj01 + 关注
实名认证
内容提供者

该用户很懒,什么也没介绍

1亿VIP精品文档

相关文档