- 8
- 0
- 约4.85千字
- 约 7页
- 2015-09-29 发布于湖北
- 举报
刍议变电运行设备的维护技术.pdf
刍议变电运行设备的维护技术
王永荣
(江苏省电力公司盐城分公司)
摘要:随着网络的发展趋势,人们对变电运行的计算机管理的要求逐
步加升.利用面向对象的开发方法和对象式包装程序设计为基础,将
数据与系统图形相结合,大大提高了管理人员的工作效率。变电运行
属于综合性电力学科,其涉及到的内容是多个方面的,对于整个电力
行业而言都有着较大的影响。下文以变电运行的安全保证、设备检修
和进行分析。
关键词:变电运行设备;维护技术;措施
Abstract: along with the development of the network trend and peopleof the substation
operationofthe computermanagement requirements gradually addup. Useofobject-oriented
development method and object type packing proceduredesign asthe basis,the data and
systemcombined with graphics, greatly improving the management work efficiency. A
comprehensivepower substation running belongto discipline,itinvolvesthe content ismoreof,
forthe wholeof the electric powerindustry hasgreat influence in. Below to the safety of the
substation running guarantee,equipment maintenanceand analysis.
Key words: the substation running equipment; Maintenance technology; measures
中图分类号:TM411+.4 文献标识码:A 文章编号:
0
0
00引言
电力系统是由发电厂、变电所、输电线、配电系统及负荷组成,
是最重要、最庞杂的工程系统之一。发电厂负责完成发电任务,而变
电站则将电力系统中的高压交流电进行变电和配电处理。所以变电
站、所的安装质量的优劣,直接影响着电力系统本身的正常和安全运
行,与此同时,其也对社会经济的正常发展和人民群众的财产生命安
全有着重大的影响。所以,我们需要认真地对待变电站、所内设备的
安装调试和运行维护工作,将事故发生的可能性降到最低,因此,变
电站、所中电力设备的安装调试和运行维护变得越来越重要。
1
1
11常见影响运行设备的安全故障检测与排除
1.1负载短路或接地。当变压器发生短路或接地时,变压器承受相
当大的短路电流,内部巨大的电动力会使绕组变形及油质劣化。因此
应安装短路保护,一般在高压侧采用跌落式熔断器,低压侧采用空气断
路器。熔断器的熔丝选择应合理,保证变压器内部短路时能熔断,或低
压侧短路或过载时能跳开。
1.2过电压的影响。变压器的高压侧进线,大多由架空线引来,很容
易遭到雷击。此外,由于断路器的正常操作、系统设备故障或其它原
因使系统参数变化,引起电网内部电磁能量的转化,出现异常电压升高,
会危及变压器内部绝缘,甚至烧毁变压器。因此,应在变压器高低压侧
均装设避雷器,并在雷雨季节来临前对其进行检测。
1.3 当线路逐次拉合后,光字信号一直未消失,则此时应考虑两条
以上线路同名相同时有接地或在开关至母线之间有接地现象(后者经
对站内设备的巡视检查可以及时发现),当然这种情况首先要排除主变
35kV进线侧线路无故障,而且类似这种多条线路同名相接地的状况并
不多见。
1.4 在倒母线一次操作刀闸以前,要先投入母差非选择性压板,并
取下母联130 开关操作保险。母联开关除有一个充电保护外,没有其
它保护,在这里取下其操作保险,目的是防止其它保护(如母差保护)误
动跳开了母联开关,若两条母线电压不平衡时合刀闸产生大电流会形
成弧光短路,发生事故。
2
2
22设备检修保证安全的技术措施
2.1验电
要检修的电气设备和线路停电后,在装设接地线之前必须进行验
电,通过验电可以明显的验证停电设备
原创力文档