THANK YOU SUCCESS * * 可编辑 Check first, that the AVR is not being affected by adverse environmental conditions :- Excessive temperature :- this means the LOCAL ambient temperature, which may be affected by heat in the terminal box, or from engine systems (turbo chargers or exhausts).close to the terminal box. Excessive vibration :- the AVR MUST be mounted on suitable anti-vibration mounts when installed in the terminal box. High Humidity :- Although encapsulated against humid conditions, terminal connections can become corroded or ‘track’ under extreme conditions, especially in