36 3 Vol.36 No.3 Feb.5, 2016 2016 2 5 Proceedings of the CSEE ©2016 Chin.Soc.for Elec.Eng. 853 DOI 10.13334/j.0258-8013.pcsee.2016.03.030 0258-8013 (2016) 03-0853-08 TM 85 ( 518055) Numerical Calculation and Experimental Study of Positive Onset Voltage of Coated Conductors YI Yong, ZHANG Chuyan, CHEN Zhengying, WANG Liming (Graduate School at Shenzhen, Tsinghua University, Shenzhen 518055, Guangdong Province, China) ABSTRACT: Conductors are coated by room temperature vulcanized silicone rubber (RTV) or ice-phobic coating in EHVDC/UHVDC power transmission lines. RTV coating is used to repair the impact induced stretches of the conductor surface and the ice-phobic coated conductors are employed on the anti-icing of transmission lines. The onset voltage of the coated conductors is higher than that of the clean conductors and the corona discharge intensity of the coated conductor is weakened. In order to analyze the positive onset voltage (POV) of the coated conductor in the corona cage, firstly, the potential gradient distribution of coated conductor was calculated in the corona cage by charge simulation method. Then, based on the classic positive onset criterion, the photoionization model considering the effective radiation wavelength of POV was 0 presented to calculate the POV of the coated conductor. The