ELECTRIC DRIVE 2013 Vo1.43 No.9 电气传动 2013年 第43卷 第9期
1
APF与SVC组合运行分析
董天兵
(广东电网公司江门供电局,广东江门529030)
摘要:有源电力滤波器(APF)与静止无功补偿装置(svc)组合运行中会相互作用,导致谐波放大甚至发生谐
振。通过分析其导致谐波放大的原因,提出通过对电容器组串联电抗器可以解决谐波放大的问题通过实验证明
该方法能够起到很好的滤波效果。同时,在实验基础上,总结了APF与SVC组合运行的最佳安装位置,进一步为
有源电力滤波器工程应用提供指导。
关键词:有源电力滤波器(APF);静止无功补偿(svc);组合运行;谐振
中图分类号:TM761.1;TN713.8 文献标识码:A
Analysis of the APF and SVC Combined Operation
DONG Tian—bing
(Jiangmen Power Supply Bureau,Guangdong Power Grid Grop,Jiangmen 529030,Guangdong,China)
一肆 。 一靼,v。
Abstract:APF and SVC will interact in the combined operation and lcad to system harmonic amplification and
resonance.The reason of causing system harmonic amplification was analyzed,then put forward series reactors in
capacitors to solve this problem.The experiment results show harmonic can be effect filtered after capacitors series
reactors.The optimal location for installed was also summarized when APF and SVC joint operation on the base of
experiment,which will guide APF further application in engineering.
Keywords:active powerfilter(APF);static vat compensator(SVC);combined operation;harmonic
1 引言
有源电力滤波器(APF)作为谐波治理装置兼
有无功补偿功能,但是APF~b偿无功所需成本很
t/ms(5ms/t~)
高,而且多数企业已经装有静止无功补偿(svc)
装置n ,因此采用APF与SVC组合运行分别进行
谐波治理和无功补偿是最佳选择。通过对APF
与SVC组合运行试验现场观察,APF与SVC会相
t/ms(5ms,格)
互作用,将高次谐波放大,严重影响APn皆波补
图1 SVC投入前后系统电流
偿效果,甚至发生并联谐振,危及设备和电网安
F