Example – High-impedance scheme CT requirements: CTs dedicated to bus protection (cannot be shared) Equal CT ratios* The accuracy class voltage rating of the CT with the lowest accuracy class above the selected voltage setting, with margin * Ratio matching covered but discouraged Application of bus protection Partial differential Loads Capacitor banks Application with overcurrent and distance relays Combined bus and transformer zone Buses with directly connected grounding transformers Application of auxiliary transformers Generally discouraged Application of bus protection Applications with p