ACTIONPAKTM MODEL AP4003-0001 Potentiometer Input, Wide Ranging, Field Configurable, Isolating Signal Conditioner Installation and Calibration Instructions Mounting All Action Paks feature plug-in installation. The AP4003-0001 uses A voltage output short circuit may cause an under range condition an 8-pin base, either the molded socket (M008) or the DIN rail socket (RED blinking at a 2Hz rate). A current output open circuit may cause (MD08). An optional retaining spring (M801) is available if required an over range condition (RED blinking at an 8Hz rate). There could for the application. be two or more LEDs blinking at the same time. That means the module has more then one error condition present. Only when all error Wiring Connections conditions have been cleared will the LEDs be back to their normal Pin Signal condition (Green ON, Red and Yellow OFF). 1 AC Power (Hot) 2 Shield (GND) 3 AC Power (Neutral) 4 Pot CCW / Shield 5 Pot Wiper 6 Pot CW 7 Output (+) 8 Output (-) Power Connections Power is connected according to the table above. The unit supports either 115VAC input (the default) or 230VAC input. For 230VAC input, the jumpers next to the input transformer (on the base board) need to be changed according to the diagram below. Switch Settings Diagnostic LEDS Other than when executing the pushbutton calibration routine, the LEDs blink under the following conditions: GREEN: 2Hz when the input is under range 8Hz when the input is over range RED: 2Hz w