IO Expander Type 2000IO 1. Installing and Operating Instructions Thank you for choosing the IO Expander. The IO Expander is used in conjunction with the 2604, 2704, 3508 and 3504 controllers to allow the number of digital IO points to be increased. There are two versions:- 1. 10 Inputs and 10 Outputs 2. 20 Inputs and 20 Outputs Each input is fully isolated and voltage or current driven. Each output is also fully isolated consisting of four changeover contacts and six normally open contacts in the 10 IO version and four changeover and sixteen normally open contacts in the 20 IO version. 1.1 Suitability When used with 2604 and 2704 controllers, software versions 5.09 and Cross Board versions 4.5 or greater must be fitted. Version 4.5 cross boards were fitted from August 2000. To check the cross board (CBC) version on the controller: 1. Enter configuration level. 2. Use and or buttons to select the INSTRUMENT Info page. 3. Use button to scroll to ‘CBC Version’. The value read in the lower right of the display should be 45 or greater. 4. Exit configuration level. The principle of this procedure is described in the 2604 and 2704 Engineering manuals, part numbers HA026761 and HA026933 respectively. When used with 3508 and 3504 controllers an IO Expander module must be fitted in the ‘J’ Communications slot 1.2 Data Transfer Data transfer is performed serially via a two wire interface as shown in Figure 1-1. ! 10/20 Inputs ! 10/20 Inputs E1 E1 J E E1 E2 E2 J F E2 IO Expander IO Expander