情境二:瞬时电流速断保护Scenario2:Instantaneouscurrentquick-breakprotection反映线路相间短路的电流保护Currentprotectionreflectinginterphaseshortcircuitofcircuit

目录页CONTENTSPAGE瞬时电流速断保护的原理及整定原则01瞬时电流速断保护的构成02Theprincipleandsettingprincipleofinstantaneouscurrentquick-breakprotectionThecompositionofinstantaneouscurrentquick-breakprotection

瞬时电流速断保护的原理及整定原则Theprincipleandsettingprincipleofinstantaneouscurrentquick-breakprotection01

瞬时电流速断保护的原理Theprincipleofinstantaneouscurrentquick-breakprotection01反映电流增大而瞬时动作原理PrincipleInstantaneousoperationreflectingtheincreaseincurrent

瞬时电流速断保护的原理Theprincipleofinstantaneouscurrentquick-breakprotection01当线路上任一点发生三相短路时,流过保护1的短路电流为:L123211QF2QF3QFGABCL1L2~?Whenathree-phaseshortcircuitoccursatanypointontheline,theshortcircuitcurrentflowingthroughprotection1is:

瞬时电流速断保护的原理Theprincipleofinstantaneouscurrentquick-breakprotection01通过保护安装处短路电流最大时的运行方式。L123211QF2QF3QFGABCL1L2~系统最大运行方式通过保护安装处短路电流最小时的运行方式。系统最小运行方式SystemmaximumoperationmodeOperationmodewhentheshort-circuitcurrentattherelaylocationismaximum.SystemminimumoperationmodeOperationmodewhentheshort-circuitcurrentattherelaylocationisminimum.

动作电流的整定原则Settingprincipleofactioncurrent023211QF2QF3QFGABCL1L2L12NM~Kop.1op.2k.max.B动作电流按躲过本线路末端可能出现的最大短路电流整定。动作电流的整定原则其中Krel取1.2~1.3SettingprinciplesforoperatingcurrentTheoperatingcurrentissetaccordingtothemaximumshort-circuitcurrentthatmayoccurattheendoftheline.whereKrelistakenwithin1.2~1.3

保护范围及灵敏度校验Protectionrangeandsensitivitycheck03瞬时电流速断保护的灵敏度,可以用保护范围的长度占被保护线路全长的百分比表示。最大保护范围应不小于线路全长的50%最小保护范围应不小于线路全长的15%~20%3211QF2QF3QFGABCL1L2L12NM~Kop.1op.2k.max.Binstantaneouscurrentquick-breakprotectioncanbeexpressedasthelengthoftheprotectionrangeasapercentageofthetotallengthoftheprotectedline.要求:RequirementThemaximumprotectionrangeshouldbenolessthan50%ofthefulllengthoftheline.Theminimumprotecti