10kV配网高压柱上式无功自动补偿装置存在的问题及处理
莫镇精
东莞安泰电业工程有限公司 广东 东莞 523000
摘 要:无功补偿装置是电力系统供电网的重要组成部分,对提高电压的稳定性、降低功率损耗和保证电站的运行具有重要意义。本文结合工程实例,探讨10kV配网高压柱上式无功自动补偿装置存在的问题,提出一些有效的处理对策,并进行系统仿真的方法,实现无功补偿装置的安全稳定运行。
关键词:无功补偿装置;问题;处理对策;零点投入;峰值投入
10 kv distribution network high post type reactive power automatic compensation device problems and processing
MoZhengJing
The dongguan Antaeus electric power engineering co., LTD. Guangdong dongguan 523000
Pick to: the reactive power compensation device of power system is an important part of the supply network, to improve the voltage stability, reduce the power loss and ensure the operation of the power station has important significance. Combining with the project examples, this paper discusses 10 kv distribution network high post type reactive power automatic compensation device problems and puts forward some effective countermeasures, and system simulation method, the reactive power compensation device to realize the safe and stable operation.
Key words: reactive power compensation device; Problem; Countermeasures; Zero investment; Peak into
无功补偿装置作为电力系统中的重要设备,具有改善电压质量、降低功率损耗和提高供电能力等作用,是保证配电网安全运行的必要措施,目前在各层次的配电网中都有安装相应容量的无功补偿装置。但在实际的运作中,由于补偿装置设计不当和人为失误的原因,时常会出现一些故障,影响到配电网的运作。因此,分析配电网无功补偿装置存在的问题,寻找有效的处理措施解决各类故障,对于实现无功补偿装置的安全可靠运行,充分发挥无功补偿装置的作用具有重要意义。
1工程案例分析
1.1工程案例
某供电公司设计并安装投运数台10kV配电网输电线路柱上式无功自动补偿装置如图1所示。
图110kV线路补偿系统图
项目设计为长距离10kV支线用户的线路无功补偿,线路谐波电流含量较小,电压畸变率可以??略,负荷运行规律平稳,自然功平均率因数为0.66,故设计无串联电抗器的2组补偿电容器,固定补偿容量设计为50kvar,主要补偿变压器的空载无功,自动补偿容量设计为300kvar,投切开关选用电容器专用JCZ5-12型真空交流接触器,每台电容器均安装外熔断器进行过流保护。装置投运后,出现故障为:300kvar电容器组在投入瞬间,正常运行的50kvar电容器的保护熔断器迅速熔断,并且部分装置的熔断器出现爆裂。针对该现象,工程技术人员感到非常困惑,不知是何原因导致正常运行电容器的熔断器出现熔断,而且现象比较剧烈。现象说明,大组投入瞬间使正在运行的小组产生了较大的涌流,但该涌流因何产生且如何解决成为困扰工程技术人员较长一段时间的问题。为解决该问题,对电路原理进行以下分析。
1.2案例分析
两组电容器补偿电路如图2所示,L1及L2是两组电容器之间各自导线或串联电抗器的电感,因为导线较短,一般每米按1~1.64mu;H计,与系统的电感LS比较时,可忽略不计。
图2中电容器组C1已投入运行,充满电荷,当电容器组C2投入瞬间,C1首先对C2充电,同时还对电感L1