grounding- m d anderson cancer center(接地-安德森癌症中心)

SECTION 26 05 26 – grounding GENERAL RELATED DOCUMENTS Drawings and general provisions of the Contract, including General Conditions and Division 01 Specification Sections, apply to this Section. Specifications throughout all Divisions of the Project Manual are directly applicable to this Section, and this Section is directly applicable to them. SUMMARY Ground the electrical service system neutral at service entrance equipment to grounding counterpoise loop. Electrical systems that are grounded shall be connected to earth in a manner that will limit the voltage imposed by lightning, line surges, or unintentional contact with higher-voltage lines and that will stabilize the voltage to earth during normal operations. Provide a completely grounded system in accordance with Article 250 of the NEC. Metal water piping system(s) installed in or attached to a building or structure shall be bonded to the service equipment enclosure, the grounded conductor at the service. Where installed in or attached to a building or structure, a metal piping system(s), including gas piping, that is likely to become energized shall be bonded to the service equipment enclosure, the grounded conductor at the service. The bonding jumper(s) shall be sized in accordance with Article 250 of the NEC. Ground each separately-derived system neutral to separate ground buses that are installed in nearest electrical rooms. Transformers, UPS systems, power conditioners, inverters, or other power supplies that are separately derived systems. Standby or emergency generators are separately derived systems if the neutral is bonded to the generator frame and if there is no direct connection of the generator neutral conductor to the service neutral conductor. Concrete reinforcing bars shall be permitted for grounding. Connect the structural metal frame to the reinforcing bars of concrete-encased electrode. Concrete-encased electrodes of existing buildings or structures shall not be required to be part

您可能关注的文档

文档评论(0)

guanjie8song + 关注
实名认证
文档贡献者

该用户很懒,什么也没介绍

1亿VIP精品文档

相关文档